To: Board of Directors
From: Peter Holzmeistr
Date: November 14, 2003
Subject: Barbara Terry billing dispute
Why this matter is before the board: Barbara Terry appeared at the last board
meeting to dispute a back electric bill she had received from the District. The board
referred the matter to me to attempt to resolve the dispute and asked me to report back
to the board.
History: On September 30, 2003, we discovered that the electronic device that allows
us to read Ms. Terry's electric meter remotely had underread her meter. The electronic
module reading was compared to the actual meter and the meter was found to have
recorded an additional 9,961 kilowatt-hours above what she had been billed. We tested
the actual meter and found it to be better than 99% accurate. That led us to conclude
that the meter reading was accurate, but the electronic module for remote read had
failed. We billed Ms. Terry $1,027.77 for the 9,961 Kilowatt-hours. Ms. Terry disputed
the back bill.
New information: Attached is a copy of our policy dealing with meter errors. Section
7.72.090.3 says if we find an error in reading a meter and we cannot clearly identify the
date the error occurred, we correct the error by recalculating the bill, but the period of the
back bill shall not exceed six months.
Our earlier back bill of 9,961 Kilowatt-hours to Ms. Terry covered a period of 21 months.
I prorated that bill over six months and came up with a bill of $309.33 (9,061 KWH / 21
months X 6 months X $.10869 = $309.33)
1 met with Ms. Terry and she was satisfied with a back bill of$309.33. She paid it in full.
7.72.090 Meter Errors
7.72.090.1 Where, in the opinion of the District, appropriate tests reveal that a meter is registering
more than two percent (2%) fast, the District will refund to the customer the amount of the
overcharge based on corrected meter readings for the period the meter was in use, but in no
instance exceeding six (6) months.
7.72.090.2 Where, in the opinion of the District, appropriate tests reveal that a meter is registering
more than two percent (2%) slow, the District will bill the customer for the amount of the
undercharge based on corrected meter readings for the period the meter was in use, but in no
instance exceeding three (3) months.
7.72.090.3 If it is discovered that an error has been made in reading a customer's meter,the District
will correct its error by recalculating the charges back to the date such error occurred. If the date the
error occurred cannot be clearly identified, the recalculation period shall not exceed six months.
The customer's account shall then be charged or credited for the amount determined. If the
calculation results in a charge to the customer, the customer shall be given a reasonable period of
time to pay the amount owed.
xbsl —y
Q xW
T RUQKE E September 30,2003
DO
Barbara Terry
11464 Chalet Rd
Sat&W SmtelvaajF--% a Truckee CA 96191
Subject: Acct#6832420001/11464 Chalet Rd
Dear Ms.Terry:
&minces Ojficc
11570 Donner Pass Road Truckee, California On September 2,2003,we sent a meter reader to the above-mentioned home to check the
reading for your account. The radio reading we had obtained in the prior month was quite
Mailing Aaasm low for a full time resident. The meter reader went directly to the meter rather than reading
Post Office Boa 309 the meter by radio,which is the norm At the meter,the meter reader found that the readings
Truckee that we have been receiving via radio did not match the dials on the meter.
California 96160
The meters we presently use have both a mechanical dial type kilowatt hour(KWH)register
TeL-pbnna and an electronic(ERT)module that independently.stores readings for remote radio reading.
(530)587-3896 The ERT module contains two tight emitting diodes and one optical pickup. The underside of
the rotating disk in the meter is painted with a non-reflective stripe and when it moves past the
w .tdpud.org optical pickup,the ERT module counts the change in light as one revolution on the disk. This
data is then stored in a register inside the ERT and is downloaded to a portable radio receiver
as a KWH reading.
In about one in every 1,000 meters,the optical pickup will fail to count every revolution of
the disk. This can be caused by excessive ambient light,a problem with the non-reflective
coating,or an intermittent failure of the electronic register. This problem can go undetected
until a manual reading is done,in which the ERT reading and the mechanical dial reading are
compared. When a mismatch is discovered,the meter is replaced and the old meter is then
tested for accuracy and scrapped. It is never returned to service.
' In all of these cases so far,the ERT reading is always less than the reading on the mechanical
dial register. Since the dials are a mechanical geared mechanism,there is no way for them to
miss"revolutions. Based on this fact,we use the dial reading as a valid indication of the
actual amount of power used and adjust the bill accordingly.
Depending on the length of time the condition has existed,the amount of`tinder registration"
and subsequent under billing can become significant. In your case,the difference between the
ERT reading and the mechanical dial reading was 9961 KWH. The enclosed bill reflects that
usage. Because this back bill is substantial,we will be happy to offer you a payment plan for
the back charges. Simply call our office to make payment arrangements.
Should you have any questions regarding this bill/letter,please do not hesitate to call us.
Sincerely,
Russian Matlock
Customer Billing Supervisor
BOARD OF DIRECTORS
Jwcpb R Ague- ...
J.RaaalJ flemig
James A.Maass
Patricia S.Sutton
Nilson mars Gandy
GENERAL MANAGER
Prier L Holzinewter
Barbara Terry-Acct#6832420001
11464 Chalet Rd
Backbill for ERTJDial Mismatch
9961 kwht2t months=474.34 kwh per month avg
Blum MONTHS KWH RATE TOTAL
Jan 2002 474 8.09263 43.91
Feb-Dec-2002 5218 0:09963 519.87
Jan-Sep 2003 4269 4D.10869 464.00
"TOTAL BACK BILL 9961 $1,027.77
Truckee Donner Public Utility District Board of Directors
Joseph R.Aguera
J.Ronald Hemig
Business Office (530) 587-3896 FAX (530) 587-5056 James A.Maass
Patricia S.Sutton
Nelson Van Gundy
General Manager
September 30, 2003 Peter L.Holzmeister
Barbara Terry
11464 Chalet Rd
Truckee CA 96161
Service Location: 11464 Chalet Rd
Meter Number: A09345
Dear Mrs. Terry:
The electric meter at the above mentioned location has been removed and tested by the District
and the following information was obtained.
Date of Test: September 9, 2003 Percentage of Accuracy
As found Full Load 99.99
Light Load 99.75
Truckee Donner Public Utility regulations for electric service as well as the State of California
Public Utilities Commission require that when, as a result of any meter test, a meter is found to
be more than 2% fast, the District will make a refund to the customer for over charges.
Based on the above information,we have determined that your meter was found to be in proper
working order.
Should you have any questions,please do not hesitate to call me at the above telephone number.
Sincerely,
Vl�w&�Jia
Vern Smith R
Electrician/Meter Technician
Post Office Box 309 11570 Donner Pass Road Truckee,California 96160
f � r
Truckee Donner Public Utility District Board of Directors
Joseph R.Aguera
J.Ronald Hemig
Business Office (530) 587-3896 FAX (530) 587-5056 James A Maass
Patricia S.Sutton
Nelson Van Gundy
General Manager
Peter L Holzmeister
October 8, 2003
Mr. Ric d Tee
vrs arbara Terry
11464 Chalet Road
Truckee, CA 96161
Dear Mr. &Mrs. Terry:
00
Per your request, please find a listing of the history of meter readings at your home since September 21,
2001. These readings are the readings that were actually transmitted by the ERT and would not match
the meter once the ERT started to fail. I have also included a letter to you from our electrician who
tested the meter that was removed. The test results actually show that the meter was running slightly"
slower than 100%accuracy.
You mentioned that you had been taking readings yourself. By comparing your readings and the
readings on the attached list, you may be able to determine when the ERT began to fail. Additionally, in .
the future if you see anything unusual about your bill such as your bill is too high or too low, please call
us immediately so we can check it out.
We are very sorry about having to send you this billing. As a non-profit local government owned by the
community we are obligated to collect revenues from those who use the services provided by the
District. If we do not,then the rest of the customers must pay the bill.
1 I apologize for the inconvenience and frustration this problem has caused you. As I told you on the
phone, if this back billing causes a financial burden, we can certainly set up a payment arrangement.
You are entitled to appeal this issue to the Board of Directors. I have attached a copy of the Board's
procedure for appealing a disputed bill. This procedure is on the back of every bill. Unfortunately, it
was not on the back of the adjusted bill that was sent to you.
If you have any further questions or if I can be of further assistance,please do not hesitate to contact me.
Sincerely,
C 11 �Gw—y
Mary P
Administrative Services Manager
Post Office Box 309 • 11570 Donner Pass Road Truckee, California 96160
Y
TRUCKEE DONNER PUD
Barbara Terry-Meter Reading History Sept 21,2001 -Sept 17,2003
Acct#6832420001 -11464 Chalet Rd
Mismatch between ERT and Dials
Read Date Reading Bill Date Usage Billed Electric Charges Notes
9/21/2001 342 0 Visual Reading @ transfer
9/26/2001 342 9/27/2001 0 35.00 Transfer Fee Only
_10/18/2001 -891 10/31/2001 549 47.83
11/16/2001 1985 11/29/2001 1094 92.14
12118/2001 3444 12/2812001 1459 121.55
1/22/2002 4822 1/30/2002 1378 131.92
2/21/2002 5951 2/28/2002 1129 116.71
3/22/2002 6992 3/29/2002 1041 107.9
4/22/2002 7921 4/30/2002 929 96.75
e/21/2002 8628 5/30/2002 707 74.58
6/21/2002 9201 6/28/2002 573 61.20
7/22/2002 9464 7/31/2002 263 30.25
8/19/2002 9552 8/30/2002 88 12.79
9/20/2002 9850 9/28/2002 298 33.75
10/22/2002 10602 10/30/2002 752 79.0
11/20/2002 11527 11/27/2002 925 96.35
12/27/2002 12986 12/28/2002 1459 149.65 Estimated Reading due to storms
1/17/2003 13849 1/29/2003 863 98.47
2119/2003 14938 2/27/2003 1089 123.08
3/18/2003 15677 3/28/2003 739 84.97
4/17/2003 16558 4/29/2003 881 100.44
5/1912003 17445 5/29/2003 887 101.09
6/18/2003 17468 6/27/2003 23 7.00
7/18/2003 17512 7/30/2003 44 9.29
8/20/2003 17538 8/28/2003 26 7.34
9/2/2003 27499 9/27/2003 9961 See Below Meter exchange-visual read
9/2/2003 0 0 New Meter
9/17/2003 498 9/27/2003 498 1106.31 Total bill for back chgs on 9961
kWh plus 498 kWh on new mtr
Please Note: A visual reading entails a physical reading of the dials on the meter and a radio reading via
the Itron Read One Pro. The meter reader then confirms that the physical dial reading and the radio reading
from the Read One Pro match.
8 Terry Mtr Rdg Hist
TRUCKEE DONNER PUD
Barbara Terry-Meter Reading History Sept 21,2001 -Sept 17,2003
Acd#.6832420001 -11464 chalet Rd
Mismatch between ERT and Dials
Read Date Reading Bill Date .UsageBillad Electric Charges Notes
9M2001 __342 0 Visual Reading®transfer
926/2001 342 __9/27/2001 MAI Transfer Fee Only
10/182001 891 10/312001 _549 47.83
11/16/2001 1985 11/29=1 1094 921
12/182001 3444 _121284"l 1459 121.55
12212002 4822 113O2002 1378 131.92
22172002 5951 2282002 1129 116.71
327JZ002 6992 3292002 1041 107.92
422200Z 7921 4/302002 _,929 96.7
5/212002 8625 513o2002 _M7 74
6212002 9201- 628/2002- 573 6120a y
7222002 9464 - 7/812002 263
a/1912002 9552 8130=2 -0 127 L-i g
920/2002 9850 9282002 298 33.7 1. ' + 3 0
101222002 10602 10/30/2W2 752 79.0
11/20/2002 11527 11/272002 _ 925
12/27/2002 129W 12211=2 1459 1419.65 Estimated.Read'utg due to storms
1/172003 13M 1/292003 am 98.4
2119=3 14938 2272003 1-089 123.
3/182003 15677 32812003 739 84.9T
4/172003 16558 4292003 884 100.
5/192003 17445 529P2003 8" 101:MR
61=003 17468' 6272003 -23 7 L/ 7 7/182003- 17512 7/36T20a 44 9 G/ 74,
8/20/2M 17538 8)28/2003 26 t/ -7
9122003 27499 9127=3` 996T 'see Befow:.' _.Mefec ex ange-visual read
922003 0 0 New Meter
GW2003 498 9272003 498 1106.31 TOW M"Btor back digs on 9961
kWh plus 498 kWh on new mtr
Please Note: A visual reading entails a physical reading of the dials on the meter and a radio reading via
the Itron Read One Pro. The meter reader then confirms that the physical dial reading and the radio reading
from the Read One Pro match.
8 Terry Mir Rdg Hist
rig 1,9 ,.,
f
Barbara d. Terry
11464 Chalet Road
Truckee, CA 96161
(530) 582-1953
October 14, 2003
Peter L. Holzmeister
General Manager
Truckee Donner Public Utility District
P.O. Box 309
Truckee, CA 96160
Dear Mr. Holzmeister:
As I am certain you can well appreciate, the Ietter I received from your Customer Billing
Supervisor, Rosana Matlock, dated September 30, 2003 was quite disturbing. Further,
upon the advice and suggestion of Mr. Hemig to try and resolve this matter amicably, we
contacted Mary Chapman on the telephone. Quite frankly, her explanation as to the
reason for an additional billing of$1106,31 was unacceptable leaving me further upset
and chagrined.
Getting straight to the point, I am at a loss to understand why it took two years to
determine that there HAY have been a malfunction with your meter reading equipment.
Unless I am mistaken, this is your equipment and it is ygur responsibility to insure it is
working properly. The fact that there ALLY have been erroneous readings is not my
responsibility but yours.
At the same time, when reviewing the October 86' letter from Ms. Chapman regarding
usage billed from 9/26/2001 through 9/17/2003, it is obvious that only four readings
appear to be out of line with the usage experienced by other fill time residents in the
neighborhood having the same electric appliances. These involve the reading of
8/19/2002, 6/18/2003, 7/18/2003 and 8/20/2003.
Parenthetically, I hasten to note that the energy requirements in our home are primarily
served by Southwest Gas and the few electric appliances in our home are new and
extremely energy efficient. Am I being penalized for utilizing energy efficient devices?
That said, and though I strongly contest the fact that TDPUD is presently billing me for
what they claim has been an equipment malfunction for the past two years, in good faith I
am enclosing my check for $200 for the past month's usage which includes the $50,70
water charge that is the same every month.
Mr. Peter L. Holzmcister...Page two
Further, based upon my own calculations of energy usage vis-a-vis that of my neighbors,I
will agree to pay an additional $300.00 at the rate of$50.00 per month for the next six
months in addition to the normal charges billed.
I trust this is acceptable. If not,please notify the Board of Directors of my intent to
appear at that first board meeting in November to formally present this matter to the full
Board for resolution of my complaint inasmuch as I will be out of town the remainder of
this week and all of next week so I will be unable to attend the next Board meeting.
Very truly yours,
14
'ter to
Barbara Terry
Cc:
Joseph R. Aguera,
J. Ronald Hemig,
James A Maas,
Patricia S. Sutton,
Nelson Van Gundy.