HomeMy WebLinkAboutResolution 94 AttachmentsRESOLUTION NO. 94
OF THE
TRUCKEE DONNER PUBLIC UTILITY DISTRICT
AMENDING ELECTRIC SERVICE CONNECTION POLICY
TITLE 7, CHAPTER 7.56
(PREVIOUSLY ELECTRIC RULE 10 ADOPTED BY
MINUTE ORDER 88-180)
WHEREAS, there are numerous advantages to the District and to the District's customers
in promoting the undergrounding of electric system facilities, including safety, reduced
maintenance and aesthetics, and
WHEREAS, it is the intent of the Truckee Donner Public Utility District to provide
consistent, concise and understandable policies that can be clearly interpreted,
NOW, THEREFORE, BE IT RESOLVED by the Board of Directors of the Truckee Donner
Public Utility District as follows:
1. That effective this date, previous rules, regulations and
policies pertaining to electric service connections be
rescinded.
2. That Title 7, Chapter 7.56, Service Connections, copy
attached, be adopted effective this date.
PASSED AND ADOPTED by the Board of Directors at a meeting duly called and held
within the District on the 6th day of September 1994 by the following roll call vote:
AYES:
NOES:
ABSENT.•
TRUCKEE DONNER PUBLIC UTILITY DISTRICT
By
James A. Maass, President
ATTEST.
Susan M. Craig, Deputy District Clerk
smc
CHAPTER 7.56
SERVICE CONNECTIONS
Sections:
7.56.010 General
7.56.020 Requirements
7.56.010 General
7.56.010.1 Service connections
It shall be the policy of the Truckee Donner Public Utility District to require all new or
rebuild construction to be placed underground wherever practical Special circumstances
may tate underarounding rs not practical and the District reserves the right to
determine the practicality of a project
7.56.010.1(A) Overhead service facilities, at secondary voltage, 480 volts or less:
In areas supplied by the District's overhead facilities, where the District's distribution pole
line is located on a street, highway, lane, alley, or private easement immediately
contiguous and at a distance not to exceed 200 feet to the customer's premises the
District will, in accordance with the established service connection charges, furnish and
install a service drop from its pole line to a point of attachment determined by District
personnel, on the customer's building or other permanent support, said support shall be
provided by customer. Connection made at the weatherhead connecting the District's
service line to the customer's service line shall be made by District personnel.
7.56.010.1(A)(1) After application for electricity and before the customer puts up the
service and meter socket, he shall make request for a District employee to come out and
mark out on the wall where the service and meter socket are to be located. The District
reserves the right to refuse service to any customer not complying with this rule.
7.56.010.1(B)
Underaround service facilities at secondary voltages
In areas
supplied by the District's
overhead facilities where the District's existing
distribution
Dole line is located —and at a distance not
to exceed 125 feet to the customer's
,premises
the District will furnish
and install into the
customer's trench and conduit cable
from the
existina distribution
Pole line to the customer's
service entrance Service
connections
of District installed
cable shall be made
by District personnel For distances
over 125
feet the customer
shall be charged
a fee as specified in the District's
established connection charges
The trench. conduit and backfill shall be furnished by the customer at his expense from
a Place on the building designated by District personnel to a place on the pole or at the
splice box also designated by District personnel The District will provide the secondaN
splice box should one be required.
7.56.010.2 The District is not obligated to serve any customer who fails to implement and
complete all of the District's requirements for service.
7.56.010.2(A) The electric meter shall not be less than six feet nor more than eight feet
from final grade or surface.
7.56.010.2(B) Any new or upgraded service requiring a transformer rated meter, the
customer shall provide in addition to the appropriate meter socket an approved box to
house current and/or potential transformers, and provisions for mounting test switches.
The meter socket and current transformer box may be located in separate boxes or may
be housed in one box. (See FUSER standards.)
7.56.010.2(C) Any service disconnect switch used on customer's facilities shall be
Underwriter's Laboratory approved for service entrances. Consult local inspection
authorities for required service switch or circuit breaker size.
7.56.010.2(D) Consult local inspection authorities for required grounding as to conductor
size and type.
7.56.010.2(D)(1) Customer's ground and District supplied neutral must connect at some
point in the customer's service so as to prevent any possibility of a potential or voltage
between the neutral and the ground.
7.56.010.2(E) If a meter becomes inaccessible for any reason, the customer shall
promptly move the meter socket and/or service to an accessible location as required by
the District.
7.56.010.2(F) If a meter socket and/or electric service comes into disrepair for any
reason, the customer shall promptly repair the socket and/or service to applicable
standards or codes. The District will assist by disconnecting the District's cables so that
work may proceed and will connect to customer's wires, after work is completed and any
necessary inspections are made and tagged by local inspection authorities.
7.56.010.3 The District will not connect to any one building more than one service for
each voltage classification, either overhead or underground, except for the District's
operating convenience or where the customer is required by law to install emergency
lighting facilities. Connection of such service to, or disconnection of such service from,
the District's lines shall be made only by authorized employees of the District.
7.56.010.4 Service requiring a transformer bank on customer's premises
7.56.010.4(A) Where transformer capacity of 150 to 300 KVA is required and, in the
District's judgment, requires the exclusive use of a transformer bank, and such bank
cannot properly be accommodated on a District easement or right of way, such customer
shall provide a location for a two pole structure on his property, such location to be
approved by the District as to installation of facilities and access for maintenance. If such
customer does not provide such a location, then he shall instead provide a site for an
outdoor transformer station enclosure or provide an indoor transformer room or vault, in
accordance with the provisions of Section 10.5.
7.56.010.4(B) Where transformer capacity greater than 300 KVA is required and, in the
District's judgment, service to a single customer requires the exclusive use of a
transformer bank with a rating greater than 300 KVA, such customer shall provide a site
for an outdoor transformer station enclosure or provide an indoor transformer room or
vault in accordance with the provisions of 7.56.010(5) below.
7.56.010.5 Construction of transformer station enclosure or vault
If a site for an outdoor transformer station enclosure is provided, the customer shall also,
at his expense, construct the necessary concrete pad for the transformer, surface the
remainder of the area to be enclosed, and terminate his service facilities at the District
transformer terminals. Such site and related improvements shall be according to
specifications prescribed by the District. The customer will provide proper fencing for
such an enclosure at his expense, subject to specifications prescribed by the District. If
a transformer room or underground vault is provided, it shall conform to the requirements
of the District pertaining to size, ventilation and access.
7.56.010.6 Primary voltage supply to customer's premises
By means of overhead facilities wherever in the District's judgment it is practicable to do
so the District will construct a primary voltage supply line by means of overhead facilities
from its distribution pole line to the transformer bank or other terminal point installed on
the customer's premises.
7.56.0200 General Meter and Service Requirements for Permanent Electric Service
7.56.020. 1 (A) Location of meter and service
7.56.020.1(A)(1) Meter and service locations must be marked by the District for the
customer prior to customer installing them. In no instance shall the meter be enclosed.
7.56.020.1(A)(2) Any service meter box installed in an underground service shall be a
minimum of 200 amperes.
7.56.020.1(A)(3) All electrical services are to be approved and appropriately tagged by
the local inspection authorities prior to the District's connection.
7.56.020.1(A)(4) If meter is located above any deck or porch, said deck or porch must
be readily accessible from the ground by way of an outdoor stairway. A meter will not
be installed in any service above a deck or porch unless said deck or porch is fully
constructed.
7.56.020.1(A)(5) if for any reason a meter is higher than approved by the District, the
customer shall move the service and/or meter socket to a location approved by District
personnel. In the event the service cannot be moved, then the customer shall construct
and keep in good repair a walk way complete with railing to the meter location.
7.56.020.1(A)(6) All connections made by the customer at the meter base must be tight.
7.56.020.1(A)(7) In multi -occupancy buildings, all units, apartments, etc. must be
identified with their respective meters. The permanent identification must appear on both
the meter panel and the entrance to the unit before meters are set.
7.56.020.1(B) Service entrance conductors
7.56.020.1(B)(1) Consult local inspection authorities for size and type of conductors.
7.56.020.1(B)(2) Conductors shall be supplied and installed by the customer with the
exception of underground service which is supplied and installed by the District.
7.56.020.1(B)(2)(a) Minimum requirement for conductor insulation is THW 75 degrees
C thermoplastic.
7.56.020.1(C) Service conduit
7.56.020.1(C)(1) Consult local inspection authorities for size and type of conduit.
7.56.020.1(C)(2) Minimum size acceptable to the District of underground conduit shall
be 2" for a 200 amp panel. For a 400 amp panel, a 3" underground conduit is required.
7.56.020.1(C)(3) Water pipe or water pipe fittings are not permitted.
7.56.020.1(C)(4) The conduit shall be one continuous length from service head to the
meter socket.
7.56.020.1(C)(5) The service conduit shall be supplied and installed by the customer.
7.56.020.1(D) Meter socket
7.56.020.1(D)(1) Domestic, single phase, self-contained meter
7.56.020.1(D)(1)(a) 100 or 200 amp, 1201240 volt, 3 wire, with one wire as neutral - four
jaw socket
7.56.020.1(D)(1)(b) 100 or 200 amp, 1201240 volt, 3 wire, with one wire as neutral - five
jaw socket
7.56.020.1(D)(1)(c) 320 amp, 1201240 volt, 3 wire, with one wire as neutral - special four
jaw socket
7.56.020.1(D)(2) Domestic, single phase, transformer rated meter
7.56.020.1(D)(2)(a) 200 to 800 amp, 1201240 volt, 3 wire with one wire as neutral - six
jaw socket
7.56.020.1(D)(3) Domestic, 3 phase, self-contained meter
7.56.020.1(D)(3)(a) 100 or 200 amp, 240 volt, a wire, no neutral - five jaw socket
756.020.1(D)(3)(b) 100 or 200 amp, 1201240 volt, 4 wire with one wire as neutral -
seven jaw socket
7.56.020.1(D)(3)(c) 100 or 200 amp, 1201208 volt, 4 wire with one wire as neutral -
seven jaw socket
7.56.020.1(D)(3)(d) 100 or 200 amp, 2401480 volt, 4 wire -with one wire as neutral -
seven jaw socket
7.56.020.1(D)(3)(e) 100 or 200 amp, 2771480 volt, 4 wire with one wire as neutral -
seven jaw socket
7.56.020.1(D)(4) Domestic, 3 phase, transformer rated meter
7.56.020.1(D)(4)(a) 200 to 800 amp, 240 volt, 3 wire, no neutral - eight jaw socket
7.56.020.1(D)(4)(b) 200 to 800 amp, 1201240 volt, 4 wire with one wire as neutral - 13
jaw socket
7.56.020.1(D)(4)(c) 200 to 800 amp, 2401280 volt, 4 wire with one wire as neutral - 13
jaw socket
7.56.020.1(D)(5) The meter socket must be installed in a true vertical plane.
7.56.020.1(D)(6) The meter socket shall be located on the outside of the building and in
no instance shall the meter be enclosed.
7.56.020.1(D)(7) If District personnel see that a meter socket and/or service are in need
of repair and not being repaired, then the District shall inform the customer of the
problem, and a time limit of 90 days shall be given to the customer to make corrections.
7.56.020.1(D)(8) If the problem is not corrected within the time limit, the customer may
be disconnected.
7.56.020.1(D)(8)(a) The District reserves the right to shorten this time period if a safety
problem exists.
7.56.020.1(E) Service switch
7.56.020.1(E)(1) Any switch used shall be Underwriter's Laboratory Approved for service
entrances, and shall be of an approved rain -tight type.
7.56.020.1(E)(2) Consult local inspection authorities for required service switch or circuit
breaker size.
7.56.020.1(F) Grounding
7.56.020.1(F)(1) Consult local inspection authorities for required ground conductor size
and type.
7.56.020.1(G) Miscellaneous conditions
7.56.020.1(G)(1) All electrical services are to be tagged by the Building Department prior
to TDPUD connection.
7.56.020.1(G)(2) Any conditions not covered above must be approved by the County
Building Inspector and a representative of the TDPUD before they are installed.
7.56.020.2 Permanent Overhead Service Requirements
7.56.020.2(A) No periscope of service conduit through roof will be permitted with the
following possible exceptions:
7.56.020.2(A)(1) A round or octagonal shaped building with a corresponding shaped roof.
7.56.020.2(A)(2) A building with a flat roof designed to roll water and carry the weight
of snow.
7.56.020.2(A)(3) It is the customer's responsibility to check first and obtain written
approval of any exceptions to this rule.
7.56.020.2(B) The required ground clearances for conductors shall be maintained as per
the attached drawing - see drawing "A".
7.56.020.2(C) Customer shall furnish and install an approved rain -tight service or
weatherhead at a point suitable for connecting the customer's service entrance
conductors to the District's conductors.
7.56.020.2(D) The point of attachment must be located as designated by District
personnel.
7.56.020.2(E) Eye bolts or equally secured means are required for the support of the
service drop. Eye bolts or clevises will be supplied by the District, but must be installed
through a minimum of 2" x 4" backing. Lag screws are not permissible.
7.56.020.2(F) Customer shall leave a minimum of 18" of conductor protruding beyond
the weatherhead of an overhead service.
7.56.020.3 Permanent Underground Service Requirements
7.56.020.3(A) All required trench clearances shall be maintained as per California Order
128, unless superseded herein.
7.56.020.3.(B) Telephone and TV cable will be allowed in the same trench, in their
respective conduits, with the District's service cable.
7.56.020.3(C) No water or sewer lines are permitted in the same trench with the District's
service cable.
7.56.020.3(D) _
PF:- -- - -
- - - agall jA^- - - - -
If a pole is needed as a result of not being able to trench, bore or obtain the necessa►y
Permits fora road crossing, the District will install the riser pole and necessary hardware
and anchors The customer shall pay to the District all actual costs for the District to
install the Dole to include the cost of the pole, hardware. anchors rh
labor and oveeads
The District will be responsible for the riser on the pole (with the exception of the first 10
feet and the span of secondary conductor between the distribution system and the riser
pole if within the 125 foot limit as referenced in Section 7,156.010., 1(8) If —the customer's
service entrance rs greater than 125 feet from the distribution system the customer will
PiRy o the District �n add�tron t the charges referenced in this section the fee for
additional footage as referenced in Se tion 7.56. 010 I
7.56.020.3(D)(2) Said pole shall be of sufficient height to provide the District's conductors
a legal clearance above the roadway.
7.56.020.3(E) Minimum trench depth shall be three feet (36').
7.56.020.3(F) The trench shall be filled as follows:
7.56.020.3(F)(1) Six inches (6') of sand under conduit.
7.56.020.3(F)(2) Twelve inches (12') of sand above conduit.
7.56.020.3(F)(3) No rocks permitted in backfill over two inches (2') in size. Rule of
thumb for sizing - if you cannot completely enclose rock in your hand, it's too big.
7.56.020.3(F)(4) No waste lumber, concrete or other building products are permitted in
backfill.
7.56.020.3(F)(5) Failure to comply with the above requirements may result in the
customer redigging trench.
7.56.020.3(G) Conduit size shall be in accordance with National Electric Code for size
of wire or cable to safely carry the customer's load, unless the N.E.C. is superseded by
either state, county or Electric Utility Service Equipment Requirements Committee Rules.
However, under no circumstance shall conduit size be smaller than two inches (2') in
diameter.
7.56.020.3(G)(1) Minimum radius of bend for elbows shall be twenty four inches (24').
7.56.020.3(G)(2) All riser conduits shall be waterproofed so no water can get into
conduit.
7.56.020.3(G)(3) Risers shall be strapped to the pole with a minimum of three conduit
straps for the first ten foot steel section of conduit.
7.56.020.3(H) The first ten foot section of conduit up the pole must be rigid steel,
Schedule 40 minimum. The remaining conduit may be PVC -Schedule 40 or equal.
7.56.020.3(H)(1) The customer shall install such facilities to a point on such pole not less
than seven feet (7) nor more than ten feet (10) above final ground level.
7.56.020.3(1) Customer shall provide a 114" pull rope in the conduit. Ther-eged up and left at the49b-&&_.
7.56.020.3(J) Customer will, at his expense, replace any conduit or fitting that is
unusable.
7.56.020.3(K) District personnel will inspect the conduit prior to backfilling.
7.56.020.3(L) Separate living units such as apartments, condos, townhouses, etc.
located on the same premises shall be served by a maximum of one conduit from any
one of the District's poles. In no case shall there be more than two electric conduits on
any one of the District's poles.
7.56.020.3(M) The District may elect to provide one conduit on the pole, connected to
a splice box located on the property line of two adjacent lots. In this instance, customers
of affected lands must make conduit runs to the splice box and not the pole.
(Electric Rule 10, MO88-180, MO94-38)