HomeMy WebLinkAbout14 Attachment 1 - 2022 Public Health Goals ReportTRUCKEE
D•
Public Utility
District
General Manager
TRUCKEE DONNER PUBLIC UTILITY DISTRICT
Brian C. Wright
2022 PUBLIC HEALTH GOALS REPORT
Executive
Leadership Team
Joe Horvath
Electric Utility Director/
Background
AGM
Chad J. Reed
Provisions of the California Health and Safety Code specify that larger (>10,000
Water Utility Director
service connections) water utilities prepare a special report by July 1, 2022 if water
Shanna Kuhlemier
quality measurements have exceeded any Public Health Goals (PHGs). PHGs are non -
District Clerk
enforceable goals established by the California Environmental Protection Agency's
Scott Crow
(Cal -EPA) Office of Environmental Health Hazard Assessment (OEHHA). The regulation
Chief Information
also requires that where OEHHA has not adopted a PHG for a constituent, the water
Officer
suppliers are to use the Maximum Contaminant Level Goals (MCLG) adopted by the
Steven Poncelet
PIO & Strategic Affairs
United States Environmental Protection Agency (USEPA). Only constituents which
Director
have a California primary drinking water standard and for which either a PHG or MCLG
Michael Salmon
has been set are to be addressed.
Chief Financial Officer
Jillian Steward
There are a few constituents that are routinely detected in water systems at
Director of Human
levels usually well below the drinking water standards for which no PHG nor MCLG
Resources and
have been adopted by OEHHA or USEPA including Total Trihalomethanes. These will
Risk Management
be addressed in a future required report after a PHG has been adopted.
Board of Directors
Joseph Aguera
The regulation specifies what information is to be provided in the report. If a
Jeff Bener
constituent was detected in the Truckee Donner Public Utility District's (TDPUD) water
Chrristta Finn
Kim Harris
supply between 2019 and 2021, at a level exceeding an applicable PHG or MCLG, this
Tony Laliotis
report provides the information required under the regulation. Included is the
numerical public health risk associated with the Maximum Contaminant Level (MCL)
and the PHG or MCLG, the category or type of risk to health that could be associated
with each constituent, the best treatment technology available that could be used to
reduce the constituent level, and an estimate of the cost to install that treatment if it
is appropriate and feasible.
What Are PHGs?
PHGs are set by the California Office of Environmental Health Hazard
Assessment (OEHHA) which is part of Cal -EPA and are based solely on public health
risk considerations. None of the practical risk -management factors that are considered
by the USEPA or the California Department of Health Services (CDHS) in setting
drinking water standards are considered in setting the PHGs. These factors include
analytical detection capability, treatment technology available, benefits and costs. The
PHGs are not enforceable and are not required to be met by any public water system.
MCLGs are the federal equivalent to PHGs.
PUBIC SPECIAL DISMICT
11570 Donner Pass Road, Truckee, CA 96161 1 (530) 587-3896 1 tdpud.org RCI.E. o� LFJIDEBSNIP FOUNDATION
Water Qualitv Data Considered
All of the water quality data collected by the TDPUD water utility between 2019 and
2021, for purposes of determining compliance with drinking water standards was considered.
This data was all summarized in our 2019, 2020, and 2021 Annual Water Consumer Confidence
Reports which were posted on the TDPUD website for customers to review by July 111 of each
subsequent year.
Guidelines Followed
The Association of California Water Agencies (ACWA) formed a workgroup which
prepared guidelines for water utilities to use in preparing these newly required reports. The
ACWA and California Department of Public Health guidelines were used in the preparation of
this report.
Best Available Treatment Technology and Cost Estimates
Both the USEPA and CDHS adopt what are known as BATS or Best Available Technologies
which are the best known methods of reducing contaminant levels to the MCL. Costs can be
estimated for such technologies. However, since many PHGs and all MCI -Gs are set much lower
than the MCL, it is not always possible nor feasible to determine what treatment is needed to
further reduce a constituent downward to or near the PHG or MCLG, many of which are set at
or close to zero. Estimating the costs to reduce a constituent to zero is difficult, if not
impossible because it is not possible to verify by analytical means that the level has been
lowered to zero. In some cases, installing treatment to try and further reduce very low levels of
one constituent may have adverse effects on other aspects of water quality.
Constituents Detected That Exceed a PHG or a MCLG
The following is a discussion of constituents that were detected in one or more of the
TDPUD's drinking water sources at levels above the PHG, or if no PHG, above the MCLG.
Arsenic: The MCL for arsenic is 10 parts per billion (ppb), the PHG and MCLG for arsenic is
0.004ppb. We have detected arsenic in 6 of our 10 wells, Glenshire Drive Well at 8.9ppb, Martis
Valley Well at 9.9ppb, Airport Well at 6.2ppb, Old Greenwood Well at 2.6ppb, Prosser Village
Well at 2.7ppb, and Sanders Well at 8.6ppb. It is important to note that the Glenshire Drive
Well, Old Greenwood Well and Prosser Village Well are delivered through a California State
Water Resources Control Board (SWRCB) approved blending permit maintaining post blend
water deliveries with arsenic concentrations below the MCL.
The category of health risk associated with arsenic, and the reason that a drinking water
standard was adopted for it, is that continuous long term exposures to drinking water
containing arsenic levels above the MCL may increase the risk of cancer. The California Office of
Environmental Health Hazard Assessment (OEHHA) has set the PHG at 0.004ppb. The PHG is
based on a level that will result in not more than 1 excess cancer in 1 million people who drink 2
liters daily of this water for 70 years. The actual cancer risk may be lower or zero. The BAT that
we are using for this report to lower the level below the MCL to .004ppb is fixed bed adsorption
system. The estimated cost to install and operate such a treatment system on all 6 Wells that
would reliably reduce the Arsenic level to .004ppb would be approximately $8,100,000 initial
construction cost with additional estimated O&M cost of an $6,900,000 per year. This would
result in an assumed increased cost for each customer of approximately $592 per year.
RECOMMENDATIONS FOR FURTHER ACTION
The drinking water quality of the Truckee Donner Public Utility District at this time
meets all California State Water Resources Control Board and USEPA drinking water standards
set to protect public health. To further reduce the levels of the constituents identified in this
report that are already below the health -based MCLs established to provide "safe drinking
water", additional costly treatment processes would be required. The effectiveness of the
treatment processes to provide any significant reductions in constituent levels at these already
low values is uncertain. The health protection benefits of these further hypothetical reductions
are not at all clear and may not be quantifiable. Therefore, no action is proposed.
The money that would be required for these additional treatment processes might provide
greater public health protection benefits if spent on other water system operation, surveillance,
and monitoring programs.