HomeMy WebLinkAboutRES 1978-04 - Board E
ems.
RESOLUTION N0, 78A
OF THE
TRUCKEE-DONNER PUBLIC UTILITY DISTRICT
APPROVING SPECIFICATIONS
AND
CALLING FOR BIDS ON 500 kVA TRANSFORMER
WHEREAS, the Board of Directors of the Truckee-Donner Public
Ut i 1 i ty D i str i ct has determi ned the need to purchase a 500kVA Trans-
former to replace the damaged transformer at Douglas Lumber Company
Mi 1 1 ;
NOW THEREFORE, BE IT RESOLVED that the Board of Directors of
the Truckee-Donner Public Utility District does hereby approve specifi-
cations described in Exhibit "A" attached hereto and made a part hereof;
BE IT FURTHER RESOLVED that the President of the Board of
Directors of the Truckee-Donner Public Utility District is hereby
directed to issue a call for bids based on the specifications as de-
scribed in Exhibit "A," and that the date and time established for
, the bid opening is Tuesday, February 21 , 1978, at 2:00 o'clock P.M.
PASSED AND ADOPTED by the Board of Directors of the Truckee-
Donner
Public Utility l i t District at a special i a l meeting n thereof duly called
ry P 9 y
and held in the District on the second day of February, 1978, by the
following roll call vote:
AYES : Huber, Kuttel , Sutton.
NOES: None
ABSENT: None
TRUCKEE-DONNER PUBLIC UTILITY DISTRICT
s
By f�
PAT TT ON, President
ATTES •
A. M i 1 ton Seymou
-�/00
C l erk Thereof
C)mC
4W
4
EXHIBIT "A"
TRANSFORMER SPECIFICATIONS
One 500 kVA, 3 phase, 60 cycle, oil immersed, dis-
tribution, pad mounted transformer, 65 degree centigrade
rise, high voltage 12470 grounded Y/7200 volts, with two
2'% taps above and two 21% taps below normal , 95 KV BIL to
low voltage 480 Y/277 volts. Transformer to be complete
with high voltage internal fuse links. Spade type termi na-
t i ons high and 1 ow 's i de. Transformer dimensions similar to
W. E. style M-735MA56AAl . Transformer type must be on R. E.A.
list of approved material .